Coefficient of Performance – COP – Refrigerator, Air Conditioner

Article Summary & FAQs

What is the coefficient of performance of a refrigerator or an air conditioner?

The coefficient of performanceCOP, of a refrigerator is defined as the heat removed from the cold reservoir Qcold (i.e., inside a refrigerator) divided by the work W done to remove the heat (i.e., the work done by the compressor). The COP strongly depends on outside temperature and required indoor temperature. For temperature difference of about 25°C (45 – 20), the COP may be about 2.5, while for the difference of about 8 °C (30 – 22), the COP may reach 3.5.

Key Facts

  • The operating principle of refrigeratorsair conditioners, and heat pumps is the same, and it is just the reverse of a heat engine.
  • In simple words, a heat pump consumes work (electric energy) and removes heat from one side, and gives this heat to the other side.
  • From an economic point of view, the best refrigeration cycle is one that removes the greatest amount of heat from the inside of the refrigerator (cold reservoir) for the least expenditure of mechanical work or electric energy.
  • The COP characterizes the amount of heat removed from the cooler.
  • The COP for cooling mode is less than for heating mode because the work done by the compressor is utilized only during the heating mode.
  • The COP strongly depends on outside temperature and required indoor temperature. For temperature difference of about 25°C (45 – 20), the COP may be about 2.5, while for the difference of about 8 °C (30 – 22), the COP may reach 3.5.
  • The efficiency of air conditioners is often rated by the seasonal energy efficiency ratio (SEER), which is defined by the Air Conditioning, Heating, and Refrigeration Institute in its 2008 standard AHRI 210/240.
Is the COP constant?
Is the COP constant?

No, the COP strongly depends on outside temperature and required indoor temperature. For temperature difference of about 25°C (e.g., 45 – 20°C), the COP may be about 2.5, while for the difference of about 8 °C (e.g., 30 – 22°C), the COP may reach 3.5.

Is higher coefficient of performance better?
Is a higher coefficient of performance better?

Sure, higher COP means more cooling performance per unit of electricity. That’s better.

How do you calculate coefficient of performance?
How do you calculate the coefficient of performance?

You cannot calculate the COP. To calculate COP, you have to know power input and cooling output, which is not simple to calculate. The manufacturer usually gives the COP.

Coefficient of Performance – Heat Pump, Refrigerator, Air Conditioner

In general, the thermal efficiency, ηth, of any heat engine as the ratio of the work it does, W, to the heat input at the high temperature, QH.

thermal efficiency formula - 1

The thermal efficiency, ηth, represents the fraction of heat, QH, that is converted to work.

Heat Pump - Heating and Air Conditioning
Heat Pump, Refrigerator, Air Conditioner – basic principle of operation

But in heat pumps and refrigerators, the work is not output. For refrigeration or heat pumps, thermal efficiency indicates the extent to which the energy added by work is converted to net heat output. From an economic point of view, the best refrigeration cycle is one that removes the greatest amount of heat from the inside of the refrigerator (cold reservoir) for the least expenditure of mechanical work or electric energy. The relevant ratio is, therefore, the larger this ratio, the better the refrigerator. We call this ratio the coefficient of performance, denoted by COP.

The coefficient of performance,  COP, is also defined for heat pumps, but at this point, we follow the net heat added to the hot reservoir. The COP usually exceeds 1, especially in heat pumps, because, instead of just converting work to heat, it pumps additional heat from a heat source to where the heat is required.

In general, COP is highly dependent on operating conditions, especially absolute temperature and relative temperature between heat sink and system.

Coefficient of Performance – Refrigerator, Air Conditioner

The coefficient of performance, COP, of a refrigerator is defined as the heat removed from the cold reservoir Qcold (i.e., inside a refrigerator) divided by the work W done to remove the heat (i.e., the work done by the compressor).

COP - coefficient of performance - equation

As can be seen, the better (more efficient) the refrigerator is when more heat Qcold can be removed from the inside of the refrigerator for a given amount of work. Since the first law of thermodynamics must be valid also in this case (Qcold + W = Qhot), we can rewrite the above equation:

COP - coefficient of performance - equation2

For an ideal refrigerator (without losses and irreversibilities) can be derived that:

COP - coefficient of performance - equation3

These formulas are also applied for an air conditioner, which works very much like a refrigerator.

On the other hand, the COP for heating and cooling are different.

Coefficient of Performance – Heat Pump

The COP is the ratio of the heat added to the system (hot reservoir) for heating. Using the first law of thermodynamics, define COP also as the heat removed from the cold reservoir plus the input work to the input work.

coefficient of performance - heat pump - equation

For an ideal heat pump (without losses and irreversibilities) can be derived that:

coefficient of performance - heat pump - equation2

These equations must use an absolute temperature scale (Tcold, Thot), and it is only a theoretical maximum efficiency. According to the above formula, the maximum achievable COP for Thot = 35 °C (308 K) and Tcold = 0 °C (273 K) would be 8.8. But in reality, the best systems are around 4.5.

As can be seen, the COP of a heat pump system can be improved by reducing the temperature difference (Thot – Tcold). Therefore, reducing the output temperature (Thot) is very efficient but requires very efficient heat transfer from the heat pump system to surroundings (i.e., use of piped floor). An increase in the input temperature (Tcold) means, for example, an oversized ground source of heat.

Example – Heat Pump – Heating and Air Conditioning

Reversible heat pump - schematic-minA reversible heat pump has a coefficient of performance COP = 3.0 when operated in the heating mode. Its compressor consumes 1500 W of electric energy.

  1. Calculate the amount of heat (Qhot) the heat pump can add to a room?
  2. If the heat pump were turned to the cooling mode (i.e., to act as an air conditioner in the summer), what would you expect its coefficient of performance to be? Assume all else stays the same and neglect all other losses.

Solution:

From the COP, which is defined as:

coefficient of performance - heat pump - equation

the amount of heat the heat pump can add to a room is equal to:

Qhot = COPheating x W = 3 x 1500 = 4500 W   or   4500 J/s

In the case of the cooling mode, the heat pump (air conditioner) with a 1500 W motor can take heat Qcold from inside the house and then dump Qhot = 4500 W  to the hot outside. Using the first law of thermodynamics, which states:

Qcold + W = Qhot,

we obtain the heat, Qcold = 3000 W. From the definition: COPcooling = 3000/1500 = 2.

Note that, in this example we have many assumptions. For example, we assumed that the temperature difference (Thot – Tcold) is the same for both modes. But we have swapped reservoirs, without any impact on COP. It is only an illustrative example.

 
References:
Nuclear and Reactor Physics:
  1. J. R. Lamarsh, Introduction to Nuclear Reactor Theory, 2nd ed., Addison-Wesley, Reading, MA (1983).
  2. J. R. Lamarsh, A. J. Baratta, Introduction to Nuclear Engineering, 3d ed., Prentice-Hall, 2001, ISBN: 0-201-82498-1.
  3. W. M. Stacey, Nuclear Reactor Physics, John Wiley & Sons, 2001, ISBN: 0- 471-39127-1.
  4. Glasstone, Sesonske. Nuclear Reactor Engineering: Reactor Systems Engineering, Springer; 4th edition, 1994, ISBN: 978-0412985317
  5. W.S.C. Williams. Nuclear and Particle Physics. Clarendon Press; 1 edition, 1991, ISBN: 978-0198520467
  6. Kenneth S. Krane. Introductory Nuclear Physics, 3rd Edition, Wiley, 1987, ISBN: 978-0471805533
  7. G.R.Keepin. Physics of Nuclear Kinetics. Addison-Wesley Pub. Co; 1st edition, 1965
  8. Robert Reed Burn, Introduction to Nuclear Reactor Operation, 1988.
  9. U.S. Department of Energy, Nuclear Physics and Reactor Theory. DOE Fundamentals Handbook, Volume 1 and 2. January 1993.

Advanced Reactor Physics:

  1. K. O. Ott, W. A. Bezella, Introductory Nuclear Reactor Statics, American Nuclear Society, Revised edition (1989), 1989, ISBN: 0-894-48033-2.
  2. K. O. Ott, R. J. Neuhold, Introductory Nuclear Reactor Dynamics, American Nuclear Society, 1985, ISBN: 0-894-48029-4.
  3. D. L. Hetrick, Dynamics of Nuclear Reactors, American Nuclear Society, 1993, ISBN: 0-894-48453-2. 
  4. E. E. Lewis, W. F. Miller, Computational Methods of Neutron Transport, American Nuclear Society, 1993, ISBN: 0-894-48452-4.

Other References:

Diesel Engine – Car Recycling

See above:

Heating and Air Conditioning